UPS2000-G-(6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
58
When you install a transformer on the output side, you must connect the load to the pL terminal and
disable power segment.
−
Generator mode
parameter
The values include
Weak adaptability mode
,
Balance mode
, and
Strong
adaptability mode
. The default value is
Balance mode
. When the mains input
voltage quality is good, select
Weak adaptability mode
; when the quality is
average (for example, the mains input is from a high-performance generator or a
common power grid), select
Balance mode
; when the quality is poor (for example,
the mains input is from a common generator), select
Strong adaptability mode
.
The parameter is configurable after the inverter shuts down.
−
Auto check bus capa.
parameter
Determine whether to automatically check the bus capacitance upon power-on and
generate capacitance failure warnings. The values include
Disabled
and
Enabled
.
The default value is
Enabled
. If the value is
Enabled
, UPS startup takes additional
30–180 seconds. The parameter is configurable after the inverter shuts down.
−
Auto start
parameter
Determine whether to automatically start inverter output after the UPS connects to
the mains. The values include
Disabled
and
Enabled
. The default value is
Disabled
.
The parameter is configurable after the inverter shuts down.
−
No battery alarm
This parameter is set to
Enabled
by default. If it is set to
Disabled
, the
No battery
alarm
will not be reported. This parameter automatically changes to
Enabled
after
batteries are connected. It is configurable only when batteries are not connected.
If the batteries have been connected and you try to set this parameter, a message "Batteries have been
connected. This parameter cannot be set." will be displayed.
Battery Parameters Screen
The configured number of batteries must match the actual number. When the actual number
changes, change the configured number. If the configured number is less than the actual
number, the battery lifespan is shortened. If the configured number is greater than the actual
number, battery leakage may cause a fire.