Overcurrent thres.
parameter
Set an alarm threshold for battery overcurrent. On a standard model, the value
ranges from 2.0 A to 4.0 A, and the default value is 3.0 A. On a long backup time
model, the value ranges from 4.0 A to 8.0 A, and the default value is 6.0 A. The
parameter is configurable in any mode.
Equalized Charge
screen
Figure 4-38
Equalized Charge screen
−
Equalized charging
parameter
Determine whether to enable equalized charging. The values include
Disabled
and
Enabled
. The default value is
Enabled
. The parameter is configurable in any mode.
−
Time interval
parameter
Set the time interval for equalized charging. The value ranges from
30Day
to
180Day
. The default value is
60Day
. The parameter is configurable in any mode.
−
Voltage
parameter
Set the battery equalized voltage. The value ranges from 2.33 V/cell to 2.40 V/cell.
The default value is 2.35 V/cell. The parameter is configurable in any mode.
−
Max. current parameter
Set the maximum equalized current. On a standard model, the value ranges from 1.0
A to 2.0 A, and the default value is 2.0 A. On a long backup time model, the value
ranges from 1.0 A to 4.0 A, and the default value is 2.0 A. The parameter is
configurable in any mode.
−
Max. time
parameter
Set the maximum equalized charge time. The value ranges from
600Min
to
999Min
.
The default value is
960Min
. The parameter is configurable in any mode.
Float Charge
screen
Figure 4-39
Float Charge screen
−
Voltage
parameter
Set the battery float voltage. The value ranges from 2.25 V/cell to 2.30 V/cell. The
default value is 2.25 V/cell. The parameter is configurable in any mode.
−
Temp. comp.
coef. parameter
Set a float voltage correction coefficient based on the battery temperature when a
battery temperature sensor is connected. The value ranges from 0.0 mV/°C*cell to