UPS2000-G-(6 kVA-20 kVA)
User Manual
5 Operations
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
73
Figure 5-3
Connecting cables to the UPS2000-G-15 kVA/20 kVA parallel system (three-phase
input three-phase output, dual mains) equipped with no PDU
5.3.1 Starting the Parallel System
The configured number of batteries must match the actual number. When the actual number
changes, change the configured number. If the configured number is less than the actual
number, the battery lifespan is shortened. If the configured number is greater than the actual
number, battery leakage may cause a fire.