UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
120
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
range. If yes, change the
range or wait until the
bypass input recovers.
0011-01
BPS
phase
reverse
Minor
Automati
c clear
If the inverter has not started,
the system has no output, and
inverter startup is prohibited.
If the inverter has started, the
inverter still works properly,
but the system cannot transfer
to bypass mode.
Possible cause: The bypass
input three-phase sequence
is incorrect.
Measure: Check that
bypass input power cables
are correctly connected.
0012-01
BPS
neutral
loss
Minor
Automati
c clear
If the inverter has not started, the
system has no output, and
inverter startup is prohibited.
If the inverter has started, the
inverter still works properly, but
the system cannot transfer to
bypass mode.
Possible cause: The bypass
input neutral wire is not
connected.
Measures: Check that
bypass input power cables
are correctly connected.
0014-01
Start
timeout
Critical
Manual
clear/Po
wer-off
clear
The UPS cannot start.
Possible causes:
The bypass load
exceeds the rated
inverter load.
An internal fault occurs
in the UPS.
Measures:
Reduce the output load,
manually clear the
alarm, and restart the
UPS.
Contact Huawei
technical support for
repair.
0020-01
Batt.
reverse
Critical
Automati
c clear
The power supply from the UPS
and system is not affected.
Possible cause: Batteries
are reversely connected.
Measure: Check the battery
installation, and reinstall
the batteries.
0022-01
No
battery
Minor
Automati
c clear
The power supply from the UPS
and system is not affected.
Possible causes:
Batteries are not
connected.
Batteries are not
securely connected.