UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
131
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
you clear the alarm, restart
the UPS. If the alarm
persists, contact Huawei
technical support for repair.
0045-06
Critical
Possible cause: The charger
is faulty.
Measure: Contact Huawei
technical support for repair.
0045-07
Critical
Manual
clear/Po
wer-off
clear
The charger in the UPS stops.
(The 20 kVA has no action.)
Possible cause: The charger
is faulty.
Measure: Contact Huawei
technical support for repair.
0045-08
Critical
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
The charger in the UPS stops.
0045-09
Critical
Manual
clear/Po
wer-off
clear
0045-10
Critical
0049-01
Battery
qty.
wrong
Minor
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
An alarm is displayed, and the
battery service life may be
shortened.
Possible causes:
The number of batteries
is incorrectly set.
Batteries are damaged.
If batteries are fully
charged, reconnect the
batteries as soon as the
system powers off.
Measures:
Check whether the
number of batteries is
correctly set.
Check whether batteries
are damaged.
After ensuring that the
number of batteries is
correct, clear the alarm.
0060-01
Inverter
fault
Critical
Power-of
f clear
The inverter shuts down. The
UPS transfers to bypass mode or
Possible cause: The
inverter is faulty.