UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
134
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
larger-capacity UPS.
0064-02
OL
timeout
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not allowed.
Possible cause: The load
exceeds the rated bypass
loading capacity.
Measure: Reduce the load
or replace the UPS with a
larger-capacity UPS.
0065-01
Power
segment
Minor
Manual
clear/Po
wer-off
clear
In single UPS mode, the loads
connected to pL power off.
Possible cause: The load
exceeds the rated loading
capacity.
Measure: Reduce the load
or replace the UPS with a
larger-capacity UPS.
0065-02
Minor
Automati
c
clear/Ma
nual
clear
Possible causes:
The battery voltage is
below the battery
protection voltage.
The battery discharge
time exceeds the battery
protection time.
Measures:
Check the battery
voltage.
Modify the power
segment settings on the
LCD.
0066-01
Output
overload
Minor
Automati
c clear
Continuous overload causes the
UPS to transfer to bypass mode
or supply no power.
Possible cause: The load
exceeds the rated loading
capacity.
Measure: Reduce the load
or replace the UPS with a
larger-capacity UPS.
0066-02
Minor
Automati
c clear
Continuous overload causes the
UPS to supply no power.
Possible cause: The load
exceeds the rated bypass
loading capacity.
Measure: Reduce the load
or replace the UPS with a
larger-capacity UPS.
0067-01
Paral. set
failure
Minor
Automati
c clear
UPS startup is not allowed.
Possible cause: The single
UPS and parallel system
settings do not match cable