UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
137
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
An internal fault occurs
in the UPS.
Measures:
Check the
communications cable.
Contact Huawei
technical support for
repair.
0125-01
Incon.
paral.
param.
Critical
Automati
c clear
An alarm is generated, and all
the UPSs in the parallel system
cannot start inverters.
Possible cause: The parallel
parameters listed in
appendix
A Parallel
Parameter List
are not set
consistently on the UPSs.
Measure: Set the parallel
parameters consistently, or
perform parallel parameter
synchronization.
NOTE
After you perform parallel
parameter synchronization,
contact Huawei technical
support if some parallel
parameters are still
inconsistent.
0131-01
Ambient
overtemp
erature
Minor
Automati
c clear
An alarm is generated.
Possible causes:
The ambient
temperature in the UPS
equipment room
exceeds the alarm
threshold (default value:
40°C).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature
and humidity
transducer.
0133-01
Ambient
undertem
Minor
Possible causes:
The ambient