UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
140
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
abnormal, wait until the
mains input recovers.
Check whether the UPS
is in battery self-check
state.
Reduce the load or
replace the UPS with a
larger-capacity UPS.
0340-01
Maint.
breaker
ON
Minor
Automati
c clear
The UPS transfers to bypass
mode.
Possible cause: The
maintenance circuit breaker
is ON during UPS
maintenance.
Measure: Switch off the
maintenance circuit breaker
after maintenance.
61440-0
1
Flash
fault
Critical
Automati
c clear
Files may be damaged.
Possible cause: The flash
memory cannot be properly
read or written.
Measure: Contact Huawei
technical support for repair.