UPS2000-G-(6 kVA-20 kVA)
User Manual
3 Installation
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
39
Figure 3-8
Bypass backfeed protection connections for the UPS2000-G-15 kVA/20 kVA
(three-phase input single-phase output)
3.4 Check After Installation
Table 3-5
lists the check items.
Table 3-5
Post-installation check items
No.
Item
Expected Result
1
Cable routing
Cable routing meets engineering requirements.
2
Cable connections
Input cables, output cables, and battery cables are
tightened to specified torques using a torque
wrench, connected correctly, and free of damage.