UPS2000-G-(6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 10 (2017-01-19)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
66
Set a float voltage correction coefficient based on the battery temperature when a
battery temperature sensor is connected. The value ranges from 0.0 mV/°C*cell to
6.0 mV/°C*cell. The default value is 3.3 mV/°C*cell. The parameter is configurable
in any mode.
Discharge
screen
Figure 4-40
Discharge screen
−
Max. time
parameter
Set the maximum discharge time. When the discharge time reaches the value, the
UPS powers off. The value ranges from
0Hour
to
24Hour
. The default value is
16Hour
. If you set the value to
0Hour
, the discharge time is not limited. The
parameter is configurable in non-battery mode or non-battery ECO mode.
If you expect the battery discharge time to be greater than 24 hours, set
Max. time
to 0 hour.
Otherwise, the system may power off.
If you set
Max. time
to 0 hour, the battery string may remain in the small-current discharge state
according to the proportion of the battery capacity to the load power, which affects the battery
lifecycle.
−
EOD mode
parameter
Determine the power backup time. The values include
Backup time first
(ensures
system running and has a long backup time,
Table 4-5
shows the EOD setting
values),
Batt. protect first
(protects batteries and extends the battery lifespan,
Table 4-6
shows the EOD setting values), and
Balanced mode
(
Table 4-7
shows the
EOD setting values). The default value is
Backup time first
. The parameter is
configurable in non-battery mode or non-battery ECO mode. EOD is short for end
of discharge.
Table 4-5
Backup time first EOD setting values
Expected
backup
time
≤ 0.1 CA
0.1 CA to
0.5 CA
0.5 CA to 1
CA
1 CA to 3
CA
> 3 CA
Low voltage
warning
threshold
(V/cell)
1.85
1.85
1.85
1.85
1.85
EOD
threshold
(V/cell)
1.75
1.67
1.60
1.60
1.60