UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
123
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
manually clear the alarm,
and restart the UPS.
Contact Huawei technical
support for repair.
0020-01
Batt. reverse
Critical Automatic clear
The power
supply from the
UPS and system
is not affected.
Possible cause: Batteries are
reversely connected.
Measure: Check the battery
installation, and reinstall the
batteries.
0022-01
No battery
Minor
Automatic clear
The power
supply from the
UPS and system
is not affected.
Possible causes:
Batteries are not
connected.
Batteries are not securely
connected.
Measures:
Connect batteries.
Check that batteries are
securely connected.
0023-01
Batt.
overtemp.
Minor
Automatic clear
An alarm is
generated, and
the battery
lifespan is
affected.
Possible causes:
The ambient temperature
exceeds the battery high
temperature alarm
threshold (default value:
50º
C)
The battery
charge/discharge current
exceeds the upper
threshold.
Measures:
Install more cooling
equipment such as air
conditioners.
Control the battery
charge/discharge current
by reducing loads.
0025-01
Batt.
overvolt.
Minor
Automatic clear
An alarm is
generated, and
the battery
lifespan is
affected.
Possible causes:
The configured number
of batteries is less than
the actual number.
The battery string charge
voltage exceeds the upper
threshold.