UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
126
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign
objects around the fan. If
the alarm persists, contact
Huawei technical support
for repair.
0032-01
Batt. OVP
Critical Automatic clear
An alarm is
generated, and
the battery
lifespan is
affected.
Possible causes:
The configured number
of batteries is less than
the actual number.
The actual number of
batteries does not meet
specifications.
The charger is abnormal.
Measures:
Check that the configured
number of batteries
matches the actual
number.
Check that the actual
number of batteries meets
requirements.
Disconnected the external
battery charger, check
whether the alarm is
cleared. If not, contact
Huawei technical support
for repair.
0034-01
Remaining
cap. warning
Minor
Automatic clear
If no action is
taken, continued
discharge will
result in system
shutdown due to
EOD.
Possible cause:
The battery discharge
lasts too long.
The mains input is
abnormal.
The number of batteries
or battery capacity is
incorrectly set.