UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
128
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
loads.
The output has
transformer loads but the
transformer mode is not
set.
The hardware is
damaged.
Measures:
After you rectify the
fault, restart the UPS.
Check whether the load
type is supported by the
UPS.
Enable the transformer
mode.
Contact Huawei technical
support for repair.
0040-05
Rectifier fault
Critical Manual
clear/Power-off
clear/Automatic
clear
The UPS shuts
down.
The UPS
transfers to
another working
mode or shuts
down.
Possible cause: The
hardware is damaged.
Measure: Contact Huawei
technical support for repair.
0040-06
Rectifier fault
Critical Power-off clear
The UPS shuts
down.
The UPS
transfers to
another working
mode or shuts
down.
Possible cause: The
hardware is damaged.
Measure: Contact Huawei
technical support for repair.
0040-07
Rectifier fault
Critical Automatic clear
The UPS shuts
down.
The UPS
transfers to
another working
mode or shuts
down.
The charger
stops working.
Possible causes:
The ambient temperature
exceeds 40°C.
The air channel is
blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.