UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
134
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
bypass mode or
has no output
based on the
transfer logic.
technical support for repair.
0060-02
Inverter fault
Critical Power-off clear
The UPS shuts
down.
The UPS may
transfer to
another working
mode or shut
down.
Possible cause: The inverter
relay is faulty.
Measure: Contact Huawei
technical support for repair.
0060-03
Inverter fault
Critical Power-off clear
0060-04
Inverter fault
Critical Power-off clear
Possible cause: The inverter
output is short-circuited.
Measure: Rectify output port
short circuits. After you clear
the alarm, restart the UPS. If
the alarm persists, contact
Huawei technical support for
repair.
0060-05
Inverter fault
Critical Automatic clear
Possible causes:
The mains experiences
instantaneous
high-voltage impact.
The output has special
loads such as sensitive
loads and rectification
loads.
The output has
transformer loads but the
transformer mode is not
set.
The hardware is faulty.
Measures:
After you rectify the
fault, restart the UPS.
Check whether the load
type is supported by the
UPS.
Enable the transformer
mode.
Contact Huawei technical
support for repair.
0060-07
Inverter fault
Critical Automatic clear
The UPS starts
upon shutdown.
The UPS may
transfer to
Possible causes:
The ambient temperature
exceeds 40º
C.
The air channel is