UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
3 Installation
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
45
No.
Item
Expected Result
4
Labels
Labels are neatly attached to both ends of each
cable, and the information on the labels is
concise and understandable.
5
Ground cable connection
The ground cable is securely connected to the
equipment room ground bar. Measure the
resistance between the UPS ground cable and the
equipment room ground bar, which must be less
than 0.1 ohm.
6
Distances between cable ties
Distances between cable ties are the same, and no
burr exists.
7
Operating environment
Clean the conductive air and other sundries.