UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
4 Control Panel
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
61
Communication Card Screen
If an SNMP card is connected, set the following parameters:
Figure 4-27
SNMP card settings
−
IP address
parameter
Set an IP address for the SNMP card. The value ranges from
0.0.0.0
to
255.255.255.255
. The default value is
192.168.0.10
.
−
Subn. mask
parameter
Set a subnet mask for the SNMP card. The value ranges from
0.0.0.0
to
255.255.255.255
. The default value is
255.255.255.0
.
−
Gateway
parameter
Set a gateway address for the SNMP card. The value ranges from
0.0.0.0
to
255.255.255.255
. The default value is
192.168.0.1
.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-28
Modbus card settings
−
Comm. address
parameter
Set a communications address for the Modbus card over the dual in-line package
(DIP) switch on the Modbus card. The value cannot be changed on the LCD.
−
Baud rate
parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The
value cannot be changed on the LCD.
If a dry contact card is connected, set the following parameters:
Figure 4-29
Dry contact card settings