UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
4 Control Panel
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
63
Figure 4-31
Output screen
The UPS supports 208 V output. In the case of 208 V output, the power is derated to 90%. For cable
configurations and connections, see the details about 220 V output.
−
Output mode
parameter
Set the system output mode. The value is not configurable on the UPS2000-G-3
kVA/6 kVA/10 kVA. The default value is
Single-phase
. The parameter is
configurable on the UPS2000-G-15 kVA/20 kVA. The values include
Single-phase
and
Three-phase
. The default value is
Three-phase
. The input mode is identified
automatically by the system. The parameter is configurable after the inverter shuts
down.
−
Voltage level
parameter
Set the system output voltage level. The values include 208 V, 220 V (default), 230
V, and 240 V on the UPS2000-G-3 kVA/6 kVA/10 kVA. The values include 208 V,
220 V (default), 230 V, and 240 V on the UPS2000-G-15 kVA/20 kVA (single-phase
output). The values include 380 V (default), 400 V, and 415 V on the
UPS2000-G-15 kVA/20 kVA (three-phase output). After you change the voltage
level, the upper thresholds for bypass voltages restore to default values 15% and
20% respectively. The parameter is configurable after the inverter shuts down.
−
Frequency level
parameter
Set the system output frequency level. The values include 50 Hz (default), 60 Hz,
and
Automatic
. If the value is
Automatic
, the power-on bypass frequency ranges
from 40 Hz to 55 Hz, and the system output frequency is 50 Hz; if the power-on
bypass frequency ranges from 55 Hz to 70 Hz (excluding 55 Hz), and the system
output frequency is 60 Hz. The parameter is configurable after the inverter shuts
down.
−
Volt. adj. coef.
parameter
You can adjust the inverter rated output voltage. The values include ±5%, ±4%,
±3%, ±2%, ±1%, and 0% (default). Press + or – to increase or decrease the output
voltage. The parameter is configurable after the inverter shuts down.
If you set
Converter mode
to
Enabled
, the UPS cannot transfer to bypass mode or
maintenance bypass mode. If you shut down the inverter, the loads power off.
−
Converter mode
parameter
Determine whether to enable inverter mode. The values include
Disabled
and
Enabled
. The default value is
Disabled
. In converter mode, the output voltage and
frequency are fixed at the specified values. The parameter is configurable after the
inverter shuts down.
Bypass
screen