UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
4 Control Panel
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
66
−
Dis. volt. thres.
parameter
Set the lower threshold for the battery voltage when pL loading is allowed in battery
mode when power segment (not supported in a parallel system) is enabled. In
battery mode, if the battery voltage is less than this value, the UPS disconnects from
secondary loads. The value ranges from 1.90 V/cell to 2.25 V/cell. The default
value is 2.00 V/cell. The parameter is configurable in non-battery mode or
non-battery ECO mode.
−
Power segment
parameter
Determine whether to enable power segment in singe UPS mode (power segment is
not supported in a parallel system). The values include
Disabled
and
Enabled
. The
default value is
Disabled
. The parameter is configurable after the inverter shuts
down.
Self-Load
screen
Figure 4-35
Self-Load screen
−
Output power ratio
parameter
This parameter is used during the tests before shipment. The value ranges from 20%
to 100%. The default value is 80%. The parameter is configurable after the inverter
shuts down.
−
Self-load mode
parameter
This parameter is used during the tests before shipment. The values include
Disabled
and
Enabled
. The default value is
Disabled
. The parameter is
configurable after the inverter shuts down.
Others
screen
Figure 4-36
Others screen
−
Recovery delay time
parameter
Delay time that the UPS takes in transferring from battery mode to normal mode
when the mains recovers. The value ranges from
0S to 900S.
The default value is
5S
. The parameter is configurable after the inverter shuts down.
If
Recovery delay time
is set to
0S
, the actual recovery delay time is 1 second.
−
Max. BPS transfers
parameter