UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
5 Operations
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
78
The configured number of batteries must match the actual number. When the actual number
changes, change the configured number. If the configured number is less than the actual
number, the battery lifespan is shortened. If the configured number is greater than the actual
number, battery leakage may cause a fire.
If the system uses dual-live-wire input dual-live-wire output, three-phase input
single-phase output or single-phase input single-phase output, set
Output mode
to
Single-phase
. If the system uses three-phase input three-phase output, set
Output mode
to
Three-phase
.
Set
Voltage level
and
Frequency level
based on the rated voltage and frequency. In the
case of single-phase output, set
Voltage level
to 208 V, 220 V (default), 230 V, or 240 V; in
the case of three-phase output, set
Voltage level
to 380 V (default), 400 V, or 415 V.
Battery parameters are configurable in non-battery mode or non-battery ECO mode.
Set
Positive batteries
and
Negative batteries
. The value ranges from 16 to 20. The
default value is 20.
Set
Battery capacity
to the total capacity of all batteries actually connected. The value
ranges from 7 Ah to 1000 Ah. The default value is 65 Ah.
This section describes how to start the UPS2000-G-15 kVA/20 kVA (dual-live-wire input
dual-live-wire output).
Figure 5-1
Connecting cables to the UPS2000-G-15 kVA/20 kVA(dual-live-wire input
dual-live-wire output)
The colors in the figure are for reference only.