6
Three-Phase Input, Three-Phase Output, One Power Source (Factory Settings)
Connect cables based on the actual situation.
Wiring
Terminal
AC
OUTPUT
AC
INPUT
PE
External
Circuit
Breaker
Q1
K1
-
15 kVA:
50 A (D
feature);
20 kVA:
63 A (D
feature)
15 kVA:
50 A (D
feature);
20 kVA:
63 A (D
feature)
Residual
Current
Circuit
Breaker
-
300 mA -
Cable
Cross-
Sectional
Area
10 mm
2
10 mm
2
25 mm
2
Terminal
Type
OT-10
mm
2
-
M6
terminal
OT-10
mm
2
-
M6
terminal
OT-25
mm
2
-
M6-90
°
terminal
AC
input
AC
load
K1
Q1
If the customer uses 10 mm
2
five-core cables for AC
input and output, the PE cable is 10 mm
2
. In this
case, connect the cable using an OT-16 mm
2
-M6-
90
°
terminal delivered with the UPS or an OT-10
mm
2
-M6-90
°
terminal prepared by the customer.
Mains
input
Bypass
input
AC
load
K
m
1
Q1
K
b
1
If the customer uses 10 mm
2
five-core
cables for AC input and output, the PE
cable is 10 mm
2
. In this case, connect
the cable using an OT-16 mm
2
-M6-90
°
terminal delivered with the UPS or an
OT-10 mm
2
-M6-90
°
terminal prepared
by the customer.
Wiring Terminal
AC OUTPUT
AC INPUT
PE
External Circuit
Breaker
Q1
Mains K
m
1 Bypass K
b
1
-
15 kVA: 50 A (D feature);
20 kVA: 63 A (D feature)
15 kVA: 50 A (D feature);
20 kVA: 63 A (D feature)
Residual Current
Circuit Breaker
-
300 mA
-
Cable Cross-Sectional
Area
10 mm
2
10 mm
2
25 mm
2
Terminal Type
OT-10 mm
2
-M6 terminal
OT-10 mm
2
-M6 terminal
OT-25 mm
2
-M6-90
°
terminal
Three-Phase Input, Three-Phase Output, Two Power Sources