UPS2000-G-(1 kVA-3 kVA)
User Manual
3 Installing the UPS
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
22
No. Item
Acceptance Criterion
3
Cable connections for
USB ports and network
ports
Cables to USB ports and network ports are connected
correctly and securely.
4
Cable labels
Labels are neatly attached to both ends of each cable,
and the information on the labels is concise and
understandable.
5
Ground cable
connection
The ground cable is securely connected to the
equipment room ground bar. Measure the resistance
between the UPS ground cable and the equipment room
ground bar, which must be less than 1 ohm.
6
Distances between cable
ties
Distances between cable ties are the same, and no burr
exists.
7
Operating environment
Clean the conductive air and other sundries.