UPS2000-G-(1 kVA-3 kVA)
User Manual
4 Setting Control Panel
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
46
Alar
m ID
Alar
m
Cause
ID
Alar
m
Name
Alarm
Severity
Alarm Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
mode,
when the
bypass
input is
normal,
this alarm
is
generated
when the
UPS
transfers
to normal
mode
three
times
within 20
minutes
after the
UPS
transfers
from
normal
mode to
bypass
mode.
In normal
mode,
when the
bypass
input is
abnormal,
this alarm
is
generated
when the
UPS
transfers
to no
output
mode.
transfers
from
normal
mode to
bypass
mode
three
times
within 20
minutes,
the UPS
is locked
in bypass
mode.
For
normal
mode,
the UPS
transfers
to no
output
mode.
66
4
Output
overlo
ad
Critical
This alarm
must be
manually
cleared.
The bypass
overload
exceeds the
time limit.
The UPS
transfers to
no output.
Possible cause: The
load exceeds the
rated load of the
bypass.
Measure: Reduce
the load or replace
the UPS with a UPS
with a larger