UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
63
Item
1 kVA
2 kVA
3 kVA
Defend Level
IP20
9.3 Mains Input Electrical Specifications
Table 9-3
Mains input electrical specifications
Item
1 kVA
2 kVA
3 kVA
Input power
cable
Single-phase (L/N) input +PE cable
Rated input
voltage
200V AC/208V AC/220V AC/230V AC/240V AC
Input
volta
ge
rang
e
Lo
wes
t
con
vers
ion
volt
age
When the ambient temperature is 0–35°C:
160/140/120/110 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40°C:
175/155/135/125 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Lo
wes
t
reco
very
volt
age
When the ambient temperature is 0–35°C:
175/155/135/125 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40°C:
190/170/150/140 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Hig
hest
con
vers
ion
volt
age
300 V AC (tolerance ±5%, load percentage < 80%)
280 V AC (tolerance ±5%, 80% < load percentage < 100%, after 15
minutes to battery mode)
Hig
hest
reco
very
volt
age
290 V AC (tolerance ±5%, load percentage < 80%)
270 V AC (tolerance ±5%, 80% < load percentage < 100%)