UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
64
Item
1 kVA
2 kVA
3 kVA
Input power
factor
(100%
resistive
load)
> 0.99
Startup
voltage
120V-280V AC
Diesel
generator
input
capacity
Minimum 1.5 times the UPS rated capacity
9.4 Bypass Input Electrical Specifications
Table 9-4
Bypass Input Electrical Specifications
Item
1 kVA
2 kVA
3 kVA
Bypass voltage
tolerance
170V –264 V AC
Bypass frequency
tolerance
47–53 Hz or 57–63 Hz
Bypass overload
capability
110%–120%, 30 minutes
120%–130%, 10 minutes
130%–150%, 1 minute
Input mode
One mains input
The upper and lower thresholds of bypass voltage toleranceare are configurable on the LCD.
9.5 Output Electrical Specifications
Table 9-5
Output electrical specifications
Item
1 kVA
2 kVA
3 kVA
Rated capacity
1000 VA/800
W
2000 VA/1600
W
3000 VA/2400
W
Output power factor (PF)
0.8