UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
25
Display
Setting
Enable or disable the ECO function.
ENA:
Enables the ECO mode.
DIS:
Disables the ECO mode (default
value).
09: Set the highest allowable voltage in ECO mode.
Display
Setting
Press ▼ or ▲ to adjust and set the highest
input voltage in ECO mode.
13–24
:
Set the parameter based on the
preset output voltage. The value range is in
+13 V AC to +24 V AC. (The default value
is +22 V AC.)
10: Set the lowest allowable voltage in ECO mode.
Display
Setting
Press ▼ or ▲ to adjust and set the lowest
input voltage in ECO mode.
13–24
:
Set the parameter based on the
preset output voltage. The value range is
–13 V AC to –24 V AC. (The default value
is –22 V AC.)
11: Set the buzzer off function.
Display
Setting
Enable or disable the buzzer off function.
ENA
: used to enable the buzzer off
function.
DIS
: used to disable the buzzer off function.
By default, the buzzer off function is
disabled.