UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
37
Alarm
ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm
Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
mode,
when
the
bypass
input is
abnorm
al, this
alarm is
generat
ed
when
the UPS
transfer
s to no
output
mode.
66
4
Output
overloa
d
Critical
This alarm
must be
manually
cleared.
The bypass
overload
exceeds the
time limit.
The UPS
transfers to no
output.
Possible cause: The
load exceeds the
rated load of the
bypass.
Measure: Reduce
the load or replace
the UPS with a UPS
with a larger
capacity.
4.8 Alarm Indication
Table 4-7
Alarm indication
Alarm
Display (Blinking)
Buzzer
Insufficient battery capacity
Beeps once every second.
Overload
Beeps twice every second.
Battery disconnection
Beeps once every second.