UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
7 Routine Maintenance
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49
Item
Expected Result
Measures
Maintenance
Interval
Tightness of bolts on
battery terminals
The location of the
signs marked on
battery terminals
indicating tight
connections does not
change.
Take photos from
multiple angles and
contact Huawei
technical support.
Quarterly
Cables between
batteries
No cable
deteriorates and the
insulation layer does
not crack.
Replace the faulty
cable.
Quarterly
Battery voltage
Equalized
charging voltage:
14.16 V ± 0.1 V
Float charging
voltage: 13.68 V
± 0.1 V
1.
Check whether
the equalized
charging voltage
and float
charging voltage
of a battery are
normal.
2.
If the charging
voltage of a
battery exceeds
the specifications
requirement,
perform a
complete forcible
equalized
charging for the
battery, and
check again
whether the
voltage is
normal.
3.
If the fault
persists, contact
Huawei technical
support.
Quarterly
Shallow discharge
test (recommended)
Conduct a shallow
discharge test when
the UPS is backed
up to verify that the
batteries can
discharge normally.
1.
Locate the cause
when an
exception is
identified.
2.
If the fault
persists, contact
Huawei technical
support.
Quarterly
Capacity Test
(recommended)
When the UPS is
backed up, discharge
a battery to the
undervoltage alarm
threshold, to refresh
the capacity of the
1.
Locate the cause
when an
exception is
identified.
2.
If the fault
persists, contact
Yearly