4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
21
Button
Function
SELECT
Setting UPS parameters:
−
When the UPS is in standby mode or bypass mode, hold
down
SELECT
for 5 seconds to start setting UPS
parameters. Press
ON/MUTE
or
SELECT
to switching
LCD display. 10 seconds after the button is released, the
default display returns.
−
When the UPS is in normal mode or battery mode, hold
down
SELECT
for 5 seconds to start setting only for 11
UPS buzzer parameters.
Selecting the next option: During the setting of UPS
parameters, press
SELECT
for more than 3 seconds.
Release the button when you hear a beep sound to select the
next option.
ON/MUTE+SELECT
Transferring to bypass mode: When the input power supply
is normal and the UPS is started in normal mode, hold
down
ON/MUTE
and
SELECT
both for 5 seconds to
enable the UPS enter the bypass mode. If the input voltage
exceeds the acceptable range or the UPS is in frequency
conversion mode, the UPS will not enter the bypass mode.
Bypass mode: When the UPS is in bypass mode, hold down
ON/MUTE
and
SELECT
both for 5 seconds to enable the
UPS enter the invert mode.
Exiting parameter setting screens: Hold down
ON/MUTE
and
SELECT
both for 0.5 seconds to exit parameter setting
screens.
Exiting cause ID screen: Hold down
ON/MUTE
and
SELECT
both for 0.5 seconds to exit alarm cause ID
screen.
OFF/ENTER
Entering alarm cause ID screen: Hold down
SELECT
and
OFF/ENTER
both for 5 seconds to enter the alarm cause ID
screen. Press
ON/MUTE
to view the previous option. Press
SELECT
to view the next option.
4.5 Setting Parameters
There are twelve configurable parameters on the LCD. The following figures show the
parameter setting screens.