Powering On the UPS
7.1
Check that the UPS has passed all check items described in chapter 6 "Verifying the
Installation".
Press and hold the
MANUAL ON/OFF
button on each lithium battery for at least 5s
and less than 15s to activate the lithium battery.
Close the upstream AC input circuit breaker for the UPS based on site requirements
.
Start
End
No: Start the UPS
in battery mode.
Yes
Press
Start the UPS in normal mode?
The initialization screen is displayed.
Initial Startup
7.2
Parameter
Remarks
Language
You can select
Chinese
,
English
(default),
Spain
,
French
, and
Russian,
based on site requirements.
Voltage level
The values include
100 V
(default),
110 V
, and
120 V
for single-phase
output. Set it based on site requirements.
1. Incorrectly setting battery parameters compromises battery safety and battery backup time.
For details about parameter settings.
2. Set system parameters with caution because the settings determine normal UPS operation.
The settings wizard starts automatically when you start the UPS for the first time. For the non-first
startup, you can skip this chapter.
Parameter
Remarks
Frequency level
The values include
50 Hz
,
60 Hz
(default), and
Automatic
. Set it based on
site requirements. If the value is
Automatic
, the power-on bypass frequency
ranges from 40 Hz to 55 Hz (excluding 55 Hz), and the system output
frequency is 50 Hz; if the power-on bypass frequency ranges from 55 Hz to
70 Hz, and the system output frequency is 60 Hz.
Battery capacity
Battery capacity is the sum of all battery capacities, set the parameters
based on the actual battery capacity. The value ranges from 100 Ah to 1000
Ah. The default value is 100 Ah.