Perform startup operations: On the standby screen, hold  down        for more than  5 seconds. 
Release the button  when  you hear a beep sound.  The startup screen is displayed. After the UPS 
starts successfully,  it enters normal  mode. After the system runs properly, close  the UPS 
downstream AC output  switch to start loads.

12

Starting inverter

7.4

8

Shutting down the UPS

1

Shutting down the Inverter to Transfer a Single UPS to Bypass Mode

8.1

Powering Off a Single UPS

8.2

Perform "shutdown  operations"  to shut  down the UPS. On the default  screen, hold  down ESC for 
more than  5 seconds. Release  the button  when  you hear a beep tone. The  inverter shuts  down. If 
the bypass voltage  is within  the configured  range, the UPS transfers to bypass mode. If the bypass 
voltage  is beyond the configured  range, the UPS  has no  output.

1. Shut  down loads.
2. Perform "shutdown  operations"  on the UPS. The inverter  shuts  down, and the UPS  transfers to 

bypass mode. If the bypass voltage  is beyond the configured  range, the UPS  has no  output.

3. Open the upstream AC input  circuit breaker for the UPS based on site requirements,  the UPS 

downstream AC output  switch.

4. Press and hold  the 

MANUAL  ON/OFF

button  on each lithium  battery for at least 5s and  less than 

15s to power off the lithium  battery. After all indicators turn  off and fans stop, the UPS  shuts 
down and loads power off.

9

Alarm Handling

Alarm 
Name

Alarm ID 
(Alarm 
ID-Alarm 
Cause)

Alarm 
Severi-
ty

Alarm 
Clear 
Mode

Impact on the 
System

Repair Proposal

Abnormal 
mains 
volt.

0001-01

Minor

Automat
ic clear

The UPS transfers 
to battery mode.

If no battery is 
equipped, the 
UPS shuts down.

The UPS changes 
the working mode 
or shuts down.

Possible causes:

The mains voltage exceeds 144 V.

The mains voltage is less than  73 V.

The mains frequency is not in the 
range of 40 Hz to 70 Hz.

Measures:

Check whether the mains input voltage 
is less than  139 V. If not, wait until the 
mains recovers.

Check whether the mains input voltage 
is greater than  80 V. If not, wait  until 
the mains recovers.

Check the mains input frequency. If the 
mains input frequency is abnormal, 
wait until  the mains input recovers.

0001-02

Minor

0001-03

Minor

Abnormal 
BPS volt.

0010-01

Minor

Automat
ic clear

The UPS cannot 
transfer to bypass 
mode. If the bypass is 
supplying power, the 
UPS changes the 
working mode.

Possible causes:

The bypass input voltage is abnormal.

The bypass input frequency is 
abnormal.

Measures:

Check whether the bypass input 
voltage exceeds the configured range. 
If yes, change the range or wait until 
the bypass input recovers.

Check whether the bypass input 
frequency exceeds the configured 
range. If yes, change the range or wait 
until the bypass input recovers.

0010-02

Minor

Summary of Contents for UPS2000-G-3K-V1-DR

Page 1: ...ormal mode Off The UPS is not working in normal mode 3 Battery indicator On The UPS is in battery mode Off The UPS is not in battery mode Blinking The remaining battery capacity is less than 25 4 Bypass indicator On The UPS is in bypass mode Off The UPS is not in bypass mode 5 Fault indicator INFO button Steady red The UPS is faulty Blinking red The UPS generates an alarm Green The UPS is running ...

Page 2: ...urity protection mechanism supported 6 Control area network CAN communications ports 7 Parallel ports 8 Maintenance bypass port 9 Emergency power off EPO port 1 ESM dry contact output DO1 DO2 2 Communications port COM_ IN 3 Communications port COM_ OUT 4 Protective ground GND 5 Indicators 6 Button for manual power on off MANUAL ON OFF 7 ESMU port for connecting to an external power source PWR 8 Po...

Page 3: ...ing at 0 5 Hz The communication between the rectifier and the external equipmentis interrupted Fault indicator Red Steady on The rectifier locks out due to output overvoltage The rectifier has no output due to an internal fault Off The rectifier is running properly Rectifier in the PDU Silk Screen Indicator Color Status Description RUN Running indicator Green Steady on Communication is normal incl...

Page 4: ...unting brackets for the UPS 1 Before installation read the user manual carefully to get familiar with product information and safety precautions 2 Use insulated tools during installation 3 Only engineers certified by Huawei or its agents are allowed to install commission and maintain the UPS Otherwise personal injury or equipment damage may occur and the UPS faults caused are beyond the warranty s...

Page 5: ...e power off 3 When the AC input or AC output changed for details about how to change the input or output system contact Huawei technical support Do not power on the UPS directly 4 Connect the UPS output power cable to the AC OUTPUT sL terminal 4 Insert the rectifier into the PDU lock the locking latch of the rectifier and install the PDU on the rack c Install guide rails based on the actual situat...

Page 6: ...l the UPS output short circuit copper bar 2 Install cables AC output power cable AC input power cable PDU rear UPS rear Battery front UPS CAN Battery CAN Battery cable UPS input cable UPS output cable Battery cable Battery cable Battery CAN 1 2 3 4 5 7 8 9 10 11 12 13 6 ...

Page 7: ...7 Battery cable 8 UPS CAN communications cable Ethernet cable RJ45 terminal Provided by Huawei 9 Battery CAN communications cable Ethernet cable RJ45 terminal Provided by Huawei 10 Battery CAN communications cable 11 PDU PE 25 mm2 25 mm2 M6 OT terminal 4 8 N m Self provided 12 Battery PE 6 mm2 6 mm2 M6 OT terminal 4 8 N m Self provided 13 Battery PE 6 mm2 6 mm2 M6 OT terminal 4 8 N m Self provided...

Page 8: ...at the bypass component is faulty Contact 5 21 8 Battery undervoltage Contact a lower than 30 V 1 A The battery voltage is less than 47 V Contact 4 10 22 Bypass mode Contact a lower than 30 V 1 A The UPS works in bypass mode when the following conditions are met The UPS is not powered on the UPS is overloaded ECO is triggered and the UPS is manually shut down Contact 3 24 11 Battery mode Contact a...

Page 9: ...d 4 Battery cables and terminals are connected correctly and voltages comply with industry standards Passed Failed 5 The UPS is properly connected to battery strings Passed Failed 6 Input circuit breakers and load circuit breakers are OFF Passed Failed 7 Power cables and signal cables are correctly identified Passed Failed 8 Ground cables are firmly connected The voltage difference between a neutr...

Page 10: ...ents 1 Incorrectly setting battery parameters compromises battery safety and battery backup time For details about parameter settings 2 Set system parameters with caution because the settings determine normal UPS operation The settings wizard starts automatically when you start the UPS for the first time For the non first startup you can skip this chapter Parameter Remarks Frequency level The valu...

Page 11: ...enerator when a power failure occurs refer to section 10 and reset Input power limiting to the maximum output capacity of the generator and automatically control the battery charge power to avoid exceeding this limit Reset the AC input circuit breaker if its capacity is less than 75 A The value is the circuit breaker capacity A x 100 V x 80 1000 NOTE If you set Input power limiting to an excessive...

Page 12: ...off the lithium battery After all indicators turn off and fans stop the UPS shuts down and loads power off 9 Alarm Handling Alarm Name Alarm ID Alarm ID Alarm Cause Alarm Severi ty Alarm Clear Mode Impact on the System Repair Proposal Abnormal mains volt 0001 01 Minor Automat ic clear The UPS transfers to battery mode If no battery is equipped the UPS shuts down The UPS changes the working mode or...

Page 13: ...rated and the battery lifespan is affected Possible causes The battery voltage reaches the alarm threshold due to battery charging Measures Disconnected the external battery charger check whether the alarm is cleared If not contact Huawei technical supportfor repair Batt undervolt 0026 01 Minor Automat ic clear An alarm is generated and the system may shut down due to EOD Possible cause The mains ...

Page 14: ...uited Measure Rectify output port short circuits power on and restart the UPS If the alarm persists contact Huawei technical support for repair On bypass 0158 01 Minor Automa tic clear If the bypass is abnormal the UPS may power off Possible causes The inverter is not started The load exceedsthe rated inverter loading capacity The inverter is faulty Measures Check whether other alarms are generate...

Page 15: ...battery is overdischarged for a long time the battery may be damaged 2 According to the output characteristics or load characteristics of the generator an inrush current may occur when the UPS starts and the generator may fail to start In this case set the target input power value to a smaller value and gradually increase it to the specified target value by a step of 100 W 1 Check the maximum outp...

Reviews: