Step 3 Set the battery capacity.
Battery Capacity
Description
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value
increases by 50 Ah each time you
press SELECT.
Step 4 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in normal mode.
Figure 5-4 Normal mode
Step 5 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End
5.2.1.2 Cold-Starting the UPS Using Batteries
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPS. The UPS will enter the standby mode. Press and
hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Figure 5-5 Standby mode
UPS2000-G-3KRTLL
User Manual
5 Operations
Issue 01 (2020-10-26)
Copyright © Huawei Technologies Co., Ltd.
94