Name
Display
Description
Automatically
return to the
default screen
ENA: Return the default
display screen (default).
If no button is pressed
within 1 minute in any
mode, the default
screen (input voltage/
output voltage) is
displayed.
DIS: Stay on the current
screen. The display will
stay on the screen
currently turned on by
the user.
Equalized charge
voltage
● Default value: 54.0 V
● When the lithium
battery does not
communicate, the
value range is 53.5–
57.0 V. The value
increases by 0.1 V
each time you press
SELECT.
When the lithium
battery is
communicating, the
UPS automatically
adapts to the
equalized charging
voltage based on the
connected lithium
battery model. The
value is fixed and
cannot be changed.
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Issue 01 (2020-10-26)
Copyright © Huawei Technologies Co., Ltd.
49