Name
Display
Description
Altitude-based
derating
● Default value: 1000
m When the altitude
exceeds 1000 m, the
output power is
derated by 1% for
each additional 100
m. The power can be
derated down to
70%.
● Value range: 1000–
4000 m
Deep discharge
test
DIS: Disable battery
deep discharge test
(default).
ENA: Enable battery
deep discharge test.
This function can be
enabled only when the
battery SOC is 100%.
Battery string
sharing
ENA: Enable battery
string sharing (default).
DIS: Disable battery
string sharing.
Exit the setting
mode
ESC: Exit the setting
mode.
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Issue 01 (2020-10-26)
Copyright © Huawei Technologies Co., Ltd.