Alarm
ID
Alarm
Name
Seve
rity
Clearance
Condition
Trigger
Condition
Impact
on the
Syste
m
Suggestion
27
Battery
dischar
ge est
functio
n
enable
d
Mino
r
The
battery
discharge
test is
complete.
The shallow or
deep discharge
function is
enabled
manually.
The
system
transfe
rs to
battery
mode.
Measure: Switch off the
battery shallow or deep
discharge test mode.
28
The
battery
dischar
ge time
reaches
the
maxim
um.
Mino
r
Set item
05 battery
discharge
time to 0
or restart
the
inverter.
The battery
discharge time
reaches the
preset value.
The
system
cannot
supply
power
in
battery
mode.
If this
alarm
is
genera
ted in
battery
mode,
the
power
output
will be
discon
nected.
Check whether the mains
input is normal.