Alarm
ID
Alarm
Name
Seve
rity
Clearance
Condition
Trigger
Condition
Impact
on the
Syste
m
Suggestion
33
Overte
mperat
ure
Mino
r
Fan
blocked:
The
highest
temperatu
re of
internal
compone
nts is
lower
than 65°C.
Fan not
blocked:
The
highest
temperatu
re of
internal
compone
nts is
lower
than 50°C.
Fan blocked:
The highest
temperature of
internal
components
exceeds 75°C for
100 ms.
Fan not blocked:
The highest
temperature of
internal
components
exceeds 87°C for
100 ms.
If the
interna
l
temper
ature
of the
system
is close
to the
overte
mperat
ure
protect
ion
thresho
ld, a
critical
overte
mperat
ure
alarm
may be
trigger
ed and
the
system
will
transfe
r to
bypass
mode.
● Possible cause: The
temperature is too high.
Measure: Decrease the
ambient temperature or
load.
● Possible cause: The
temperature sensor is
faulty.
Measure: Send the device
to the maintenance
center.
UPS2000-G-3KRTLL
User Manual