Alarm
ID
Alarm
Name
Seve
rity
Clearance
Condition
Trigger
Condition
Impact
on the
Syste
m
Suggestion
36
Overlo
ad
Mino
r
The load
percentag
e exceeds
10%.
The load
percentage
exceeds 105%.
The
system
transfe
rs to
bypass
mode
when
the
overloa
d time
expires.
Possible cause: The UPS is
overloaded.
37
The
inverter
switch
is off in
ECO
mode.
Mino
r
The
inverter
switch is
turned on.
The inverter
switch is off in
ECO mode.
When
the
mains
input
exceed
s the
ECO
range,
the
power
supply
is
discon
nected.
The inverter output switch is
turned on.
38
The
numbe
r of
started
inverter
s is
insuffici
ent to
carry
the
load.
Mino
r
The
inverter
switches
of other
UPSs in
the
parallel
system
are turned
on.
In parallel
mode, the
number of
started inverters
is insufficient to
support the
actual load.
The
system
keeps
workin
g in
bypass
mode
and
cannot
transfe
r back
to
inverte
r
mode.
Turn on the inverter
switches of other UPSs.