Operation 

Transferring to Maintenance Bypass 
 

5.1 

Status & Indicators 

5.3 

Status 

Power Indicator (Green) 

1. The mains is normal. 
2. The mains fails but UPS is providing power. 

On 

The mains fails. 

Off 

Transferring to UPS Protection 
 

5.2 

HUAWEI TECHNOLOGIES CO., LTD. 

Huawei Industrial Base, Bantian, Longgang 

Shenzhen 518129 

People's Republic of China 

www.huawei.com 

Before transferring to maintenance bypass, ensure that the Power indicator is on. Transfer the 
rotary bypass switch from UPS to MBS. At this time, all connected devices are powered by the 
mains directly. Turn off the UPS and disconnect two cables connected to the UPS. Then you 
can maintain the UPS.  

After maintaining the UPS, ensure that the UPS operates properly. Reconnect the UPS to the 
unit by following the installation section. Verify that the Power indicator is on. Turn on the UPS, 
then transfer the rotary bypass switch from MBS to UPS. All connected devices are protected by 
the UPS. 

Slave On Indicator (Yellow) and Slave 

Output Status 

Master Load > 30 W 

Master Load < 10 W 

Master/slave 
function is enabled 

Slave On indicator 

On 

Off 

Slave output 

On 

Off 

Master/slave 

function is disabled 

Slave On indicator 

On 

On 

Slave output 

On 

On 

Summary of Contents for UPS2000-MBS-16A

Page 1: ...talling the unit ensure that the sum of the leakage currents of the unit and the devices it powers does not exceed 3 5 mA NOTICE 1 Slave outlets 2 Master outlets 3 Power indicator 4 Slave on indicator 5 Bypass switch 6 Outlet for UPS output 7 Outlet for UPS input 8 AC input 9 Circuit breaker 10 Master slave function switch Issue 01 Date 2016 03 25 UPS2000 MBS 16A PDU Maintenance Bypass Switch Modu...

Page 2: ... G 2KRTL when connecting UPS2000 G 1KRTL 1KRTS 2KRTS Refer to cable connection of UPS2000 G 3KRTL when connecting UPS2000 G 3KRTS 3 3 kVA UPS output form factor terminal or C20 varies with different actual models NOTE UPS2000 G 2KRTL UPS2000 G 3KRTL 2 Installing the Unit 3 Rack mounting Scenario Front Rear NOTICE When installing ensure that the PDU rear panel is aligned with the UPS rear panel C19...

Page 3: ...he mains is normal The Power indicator will turn off when there is a power failure 1 The master slave function is disabled by default Ensure that the master slave function switch is on the disable status before operation 2 Only when the master slave function is enabled loads connected to slave outlets will be shut down after load is detected lower than 10 W in master outlet 3 Master slave function...

Page 4: ...this time all connected devices are powered by the mains directly Turn off the UPS and disconnect two cables connected to the UPS Then you can maintain the UPS After maintaining the UPS ensure that the UPS operates properly Reconnect the UPS to the unit by following the installation section Verify that the Power indicator is on Turn on the UPS then transfer the rotary bypass switch from MBS to UPS...

Reviews: