NO TE
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-60KTTL/UPS5000-A-80KTTL/
UPS5000-A-120KTTL:
The nominal battery discharge current refers to the discharge current of thirty-two 12 V
batteries at 384 V in standard configuration.
The maximum battery discharge current refers to the EOD current of thirty-two 12 V
batteries in standard configuration, that is, one hundred and ninety-two 2 V battery
cells (1.67 V/cell).
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
The nominal battery discharge current refers to the discharge current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the EOD current of forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery cells (1.67
V/cell).
●
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables. The cables listed in the table
are used only when the following requirements are met:
–
The cables are installed along the wall or on the floor (IEC 60364-5-52 C
standards).
–
The ambient temperature is 30°C.
–
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%. The recommended cross-sectional areas in the table meet the basic
through-current requirements. Users should evaluate the line voltage loss
based on the actual cable length. If the voltage loss exceeds the
requirements, increase the cable cross-sectional areas properly.
–
Copper cables whose conductor supports the maximum operating
temperature of 90°C are used.
●
When the external conditions such as cable routing or ambient temperature
change, perform verification in accordance with the IEC 60364-5-52 or local
regulations.
●
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
●
The currents listed in the table are measured at a rated voltage of 380 V; if
the rated voltage is 400 V, multiply the currents by 0.95; if the rated voltage is
415 V, multiply the currents by 0.92.
●
When primary loads are non-linear loads, increase the cross-sectional areas of
the neutral wires by 1.5–1.7 times.
CA UTION
When you connect power cables, comply with the tightening torque listed in the
following table to ensure secure connections and prevent safety risks.
UPS5000-A-(30 kVA–120 kVA)
Quick Guide
1 Installation
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd.
9