Table 1-2 Power cable terminal requirements
Model
Port
Connection Method
Bolt
Specificat
ions
Bolt Hole
Diameter
Torque
30–40 kVA
Mains
input
Crimped OT terminal
M6
6.5 mm
4.5 N·m
60–80 kVA
Crimped DT terminal
M8
9 mm
13 N·m
120 kVA
Crimped DT terminal
M10
11 mm
27 N·m
30–40 kVA
Bypass
input
Crimped OT terminal
M6
6.5 mm
4.5 N·m
60–80 kVA
Crimped DT terminal
M8
9 mm
13 N·m
120 kVA
Crimped DT terminal
M10
11 mm
27 N·m
30–40 kVA
Battery
input
Crimped OT terminal
M8
9 mm
13 N·m
60–80 kVA
Crimped DT terminal
M10
11 mm
27 N·m
120 kVA
Crimped DT terminal
M12
13 mm
47 N·m
30–40 kVA
Output
Crimped OT terminal
M6
6.5 mm
4.5 N·m
60–80 kVA
Crimped DT terminal
M8
9 mm
13 N·m
120 kVA
Crimped DT terminal
M10
11 mm
27 N·m
30–40 kVA
PE
Crimped OT terminal
M6
6.5 mm
4.5 N·m
60–120
kVA
Crimped DT terminal
M8
9 mm
13 N·m