Figure 1-41 Marking-off template (unit: mm)
(1) Rear edge of the cabinet
(2) Wall
(3) Mounting holes for antiseismic kits
(4) Mounting hole of the L-shaped bracket
NO TE
Pay attention to the front and back edge lines of the cabinet, preventing incorrect location.
Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install
expansion sleeves in the holes.
1. Drill a hole into the concrete floor using a hammer drill. The hole depth
ranges from 52 mm to 60 mm.
2. Slightly tighten the expansion bolt and vertically insert it into the hole. Knock
the expansion bolt using a rubber mallet until the expansion sleeve is fully
inserted into the hole.
3. Partially tighten the expansion bolt.
4. Remove the bolt, spring washer, and flat washer.
NO TICE
Knock the expansion bolt into the hole until the expansion sleeve completely fits
into the hole. The expansion sleeve must be completely buried under the ground
to facilitate subsequent installation.
UPS5000-A-(30 kVA–120 kVA)
Quick Guide
1 Installation
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd.
35