No.
Item
Acceptance Criteria
13
Operating environment
The inside and outside of the cabinet are
free from conductive dust or other
sundries.
● 30 kVA/40 kVA UPS
– There is no foreign matter (such as
copper wires and screws) between
wiring terminals. Cables are
crimped according to standards,
and there is no bare copper wire.
– There is no foreign matter in the
wiring terminal box.
● 60 kVA/80 kVA/120 kVA UPS
– There is no foreign matter
between wiring terminals. Cables
are crimped according to
standards, and there is no bare
copper wire.
– There is no foreign matter at the
bottom of the UPS.
14
DIP switch settings
Toggle switch 4 is set to ON.
15
Short circuit between
copper bars
Check that copper bars are open-
circuited using a multimeter.
NO TE
● After installing cables and verifying the installation, use sealing putty to seal the gaps
between the cables and the cabinet.
● After verifying the installation, reinstall all the covers.
UPS5000-A-(30 kVA–120 kVA)
Quick Guide
1 Installation
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd.
57