UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
4 Installation Verification
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
141
Figure 4-64
Site Config. page
The default SNMP version is V3. The preset password is
Changeme1
for MD5/SHA and is
Changeme2
for DES/AES. Change the password after your first login, preventing unauthorized
access.
The standard protocols SNMP V1 and SNMP V2 have security risks. You are advised to use the
secure protocol SNMP V3.
The standard encryption algorithms MD5 and DES have security risks. You are advised to use the
secure encryption algorithms SHA and AES.
To obtain the MIB file choose
Config
>
Site Config
>
SNMP
>
Download HUAWEI_UPS_MIB
.
SNMP Trap
indicates the IP address of the server configured with NMS software. If
SNMP Trap
is
incorrectly set or not set, system information will be lost or not reported in time.
The certificate is used for Secure Sockets Layer (SSL) encryption protection during WebUI login.
Apply to a third-party institution for the certificate.
Specify
Email server IP address
,
Sender's email
, and
User account authentication required
when sending a mail
and click
Test
to check whether the test email can be received.
Configure
Alarm Notification Server
is used to configure a server for receiving alarm emails from the
monitoring system.
Set
and
Alarm Severity
and simulate an alarm. Check that the alarm email can be received.
Configure Alarm Notification Email Address
is used to configure the email address for receiving
alarm emails from the monitoring system.
4.2.5 Maint. Page
On the homepage, click the
Maint.
tab. The
Maint.
page provides the
Calib.
,
Commissioning Var.
,
Upgrade
, and
Download
tabs. The
Maint.
page consists of three parts,