UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
5 Operation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
154
Figure 5-13
AC output
Check on the WebUI
On the home page, choose
Monitoring
>
Real-time Data
. In the
Output
area, check the
UPS three-phase output voltage and frequency, as shown in
Figure 5-14
Real-time Data page
If the measured voltages are not within the normal ranges, choose
Maint.
>
Calib.
on
the WebUI and expand
Power unit
. Enter the measured voltages in
Ph. A output volt.
,
Ph. B output volt.
, and
Ph. C output volt.
under
Actual Value
, and click
Submit
to