UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
5 Operation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
163
Figure 5-24
Setting ECO mode
Step 4
Manually start the inverter.
After the inverter starts, the UPS still works in bypass mode and the inverter is standby.
shows the power flow displayed on the
System Status
screen. If the bypass is
abnormal, the inverter supplies power immediately. If the inverter is not started, the UPS may
be disconnected.
Figure 5-25
System Status screen
----End