UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
8 Technical Specifications
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
181
8.3 Safety Regulations/EMC
Safety Regulations/EMC
400 kVA
Safety regulations
EN62040-1: 2013
IEC62040-1: 2013
EMC
EN62040-2
IEC62040-2
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
IEC61000-4-4
IEC61000-4-5
EN61000-4-6
IEC61000-4-8
IEC61000-4-11
8.4 Mains Input Electrical Specifications
Mains Input
Specifications
400 kVA
500 kVA
Input format
Three-phase, four-wire, and PE wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage range
138–485 V AC
The UPS5000-A power is not derated at 305–485V AC and is
linearly derated at 305–138 V AC.
Rated frequency
50 Hz or 60 Hz
Input frequency
range
40–70 Hz
Input power factor
> 0.99 (full load); > 0.98 (50% load)
THDi
< 3% (linear full load) or < 5% (non-linear load)