3 Installation
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
78
shows the ground cable connecting to the UPS.
Figure 3-44
Ground cable
3.2.6 Connecting AC Input Power Cables
3.2.6.1 Single Mains
After connecting cables, check that a certain clearance is reserved between the internal switch
(if any) extension pole and power cables to avoid friction.
Connecting the AC input power cable to mains input power distribution terminals 1L1, 1L2,
1L3, and N respectively, as shown in