UPS5000-A-400 kVA
User Manual (50 kVA, PF=0.9)
3 Installation
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
83
When the mains input and bypass input use different power sources, you need to connect
four N wires.
After connecting cables, check that a certain clearance is reserved between the internal
switch (if any) extension pole and power cables to avoid friction.
Figure 3-49
Connecting bypass input power cables
----End
3.2.7 Connecting AC Output Power Cables
After you connect output power cables, if loads are not ready to be powered, insulate the end
of the system output power cable.