Initial Startup
a. During the initial startup, set the language, time and date, network parameters, and system
parameters on the
Settings Wizard
screen.
b. After you set parameters on the
Settings Wizard
screen, the MDU displays the
Bypass mode
and
No battery
alarms, which do not need to be handled. If there is any other alarm, you need to
rectify the fault.
c. View the system running diagram on the MDU to check that the UPS is working in bypass mode.
• The
Service Expert
app can be downloaded from Google Play and can run on Android.
• The port number is
443
by default and can be modified. If the UPS is managed using the app,
the port number must be set to
443
.