UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
98
Figure 4-25
Battery Param. screen 1
Item
Description
Installation time
A battery maintenance reminder is displayed when the
maintenance time (counted from the installation time)
comes.
Maintenance period (d)
The interval (set in days) for when the battery maintenance
reminder is generated (based on installation time).
Battery type
Set the battery type based on actual conditions. Currently,
only lead-acid batteries are supported.
Chg. cur. limiting coef.
(C10)
The charging current limit is a multiple of the battery
capacity. The value can be 0.05–0.15, and is 0.1 by default.
Cell float voltage (V/cell)
The float voltage value can be 2.23–2.27 V/cell, and is 2.25
V/cell by default. The value is configurable in any mode.
Cell equalized volt. (V/cell)
The battery equalized voltage value can be 2.30–2.40
V/cell, and is 2.35 V/cell by default. The value is
configurable in any mode.