4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
101
Figure 4-28
Battery Param. screen 4
Item
Description
Backup time warning
An alarm is generated if this parameter is set to
Enable
and the backup time is lower than the warning threshold.
Remain. cap. warning
An alarm is generated if this parameter is set to
Enable
and the remaining capacity is lower than the warning
threshold.
Dis. cur. 0.1C EOD (V/cell)
,
Dis. cur. 0.3C EOD (V/cell)
,
Dis. cur. 0.5C EOD (V/cell)
,
and
Dis. cur. 1.0C EOD
(V/cell)
By default,
0.1C EOD (V/cell)
is set to
1.80
,
0.3C EOD
(V/cell)
to
1.80
,
0.5C EOD (V/cell)
to
1.75
, and
1.0C
EOD (V/cell)
to
1.60
. These values are calculated in real
time based on the discharge currents.
Figure 4-29
Battery Param. screen 5